NPC-10V5DR Free Cooling Damper Controller

£68.00

SKU: NPC10V5DR Categories: ,

Description

The NPC-10V5DR is a Proportional Integral Free Cooling Damper Controller. Setpoint can be adjusted remotely by using Digital Remote, External Pot or 0-10VDC source. The controller has separate analogue 0-10VDC proportional output for Heating, Cooling and Damper. The controller is designed specifically to control Damper Actuators, Thyristor Controllers, Relay Modules etc.

FEATURES

  • Three Analogue outputs, 1 Heating output, 1 Cooling output and 1 Damper Actuator output
  • Digitally calibrated 0-10VDC proportional outputs
  • Separate output for Heating, Cooling and Dampers, i.e., Plug n Play, no configuration required
  • Full Proportional + Integral action. Integral action can be switch off if not required
  • User friendly Back-lit 16X2 LCD Display with 5Way Navigation Switch
  • Temperature and Setpoint range from -5°C to +95°C with a resolution of 0.1°C. Min and Max Setpoint range is user adjustable
  • Temperature Sensors offset feature. With this feature, individual offset of ±5°C with a resolution of 0.1°C can be adjusted to eliminate error for Return Air and Outside Temperature Sensors.
  • Night Set-back Input
  • Remote Setpoint input, i.e. Two-wire Digital, Resistive 0-10KΩ, 1-11KΩ etc. and Analogue 0-10VDC
  • 24VAC/DC Power input
  • Din-rail PCB Holder

 

Specifications

 

Power Supply 24VAC/DC, -15/+10%  130mA max
Temperature and Setpoint Range -5°C to 95°C, 0.1°C Resolution
Return and Outside Sensors NTC 10K3A1, Offset is user adjustable ±5°C, 0.1°C Resolution
Integral Time (Heating & Cooling) 0 to 500seconds
Proportional Band (Prop band) 0-50°C, 1°C Resolution
Deadband 0-10°C, 1°C Resolution
Night Set-back -5°C to 95°C, 0.1°C Resolution
External Setpoint Input Digital Remote, Ext. Pot/0-10VDC
External Pot Resistance User selectable from Menu: 0-10KΩ, 1-11KΩ, 0-5KΩ and 560Ω-10560Ω
External Pot Setpoint Range User selectable: ±4°C, ±5°C, ±10°C, ±20°C, 5/35°C, -5/45°C, 0/50°C, -10/50°C, 30/90°C, 40/90°C, 25/95°C, -5/95°C
External 0-10VDC Setpoint Range User adjustable: anywhere between -5°C to 95°C with minimum difference of 1°C
Digital Remote Range (Setpoint Adjuster) User adjustable: anywhere between -5°C to 95°C with minimum difference of 1°C
Proportional Outputs (Heating, Cooling & Damper Actuator) Digitally Calibrated 0-10VDC, 5mA per output max at 10VDC
Dimensions 113 x 82 x 47 (W x H x D)

NPC-10V5DR Free Cooling Damper Controller Data Sheet

Download
X